Low MOQ for Zst Types Glass Bulb Fire Sprinkler – Special response sprinkler bulbs (short type) – Zhurong
Low MOQ for Zst Types Glass Bulb Fire Sprinkler – Special response sprinkler bulbs (short type) – Zhurong Detail:
Size(mm) | Temperature Rating(℃/°F) | Color | |
A | 3.8 | 57℃ / 135°F | orange |
B | 2.02 | 68℃ / 155°F | red |
C | <4.5 | 79℃ / 175°F | yellow |
D | 5±0.1 | 93℃ / 200°F | green |
d1 | 5.1±0.2 | 141℃ / 286°F | blue |
d2 | 5.1±0.3 | ||
L | 19.8±0.5 | ||
l1 | 16±0.4 | ||
l2 | 15.8±0.4 | ||
Glass bulb load(N) | Average Cursh load(X) | 4000 | |
lower Tolerance Limit(TL) | ≥2000 | ||
Maximum clamping torque | 8.0 N·cm | ||
Response time index(m*s)0.5 | 80<RTI≤350 |
Although it is smaller, each product is subject to strict factory inspection before leaving the factory, including appearance, size, static action temperature and crushing load test.
During the static action temperature test, the test ambient temperature is (20 ± 5) ℃, and the test is carried out in liquid bath. Water bath (distilled water is preferred) shall be adopted for glass bulbs with nominal operating temperature not higher than 79 ℃, and oil bath (oil products suitable for nominal operating temperature) shall be adopted for glass bulbs with nominal operating temperature higher than 79 ℃. The temperature of the test liquid bath shall be uniform, the temperature deviation in the test area shall not exceed 0.5 ℃, and the temperature measurement accuracy shall not be less than ± 0.1 ℃.
Place the glass bulb sample vertically in the liquid bath. The distance between the center of the glass bulb and the liquid level is not less than (40 ± 5) mm. Raise the temperature from room temperature to (20 ± 2) ℃ lower than the nominal operating temperature at a heating rate of not more than 20 ℃ / min. after holding for 10 minutes, raise the temperature at a rate of 0.4 ℃ / min ~ 0.6 ℃ / min until all the samples are broken. Record the operating temperature of each sample, Judge whether the test results exceed the following temperature range:
X ±(0.035X + 0.62)
X — Nominal operating temperature, unit: Celsius (℃).
Product detail pictures:
Related Product Guide:
We have state-of-the-art tools. Our products are exported towards the USA, the UK and so on, enjoying a fantastic reputation amongst customers for Low MOQ for Zst Types Glass Bulb Fire Sprinkler – Special response sprinkler bulbs (short type) – Zhurong , The product will supply to all over the world, such as: Amsterdam, Macedonia, Belgium, We welcome you to visit our company and factory. It is also convenient to visit our website. Our sales team will offer you the best service. If you need more information, please feel free to contact us by E-mail or telephone. We are sincerely hope to establish a good long-term business relationship with you through this opportunity, based on equal, mutual benefit from now till the future.